3 phase mineral oil immersed power transformer-41

Transformer

Home >  Products >  Transformer

3-phase mineral oil-immersed power transformer

Product Description

· KS 11 series mining transformers are suitable for the central substation of underground coal mine, well bottom yard, total air duct and main air duct. There is gas but no explosion risk. It is also suitable for the more humid environment of tunnels.

· Normal environment use conditions: the altitude shall not exceed 1000m. The ambient temperature was maximum + 40℃ and minimum-25℃.

· Special environment conditions: altitude over 1000m.

·The ambient temperature was maximum + 40℃ and minimum-45℃.(Details when ordering) · The relative humidity of the surrounding air is not greater than 95% (+ 25℃).

· No strong turbulence and the inclination with the vertical surface not exceeding 35°.

mutil_pix

Executive Standard

·JB/T 3955-2006 Power transformer

·GB 1094.1-2003 Power transformer

·GB/T1094.3-2003 Power transformer

·GB 1094.5-2008 Power transformer

·GB1094.2-2013 Power transformer

·The international standard IEC76

3-phase mineral oil-immersed power transformer factory

Performance Characteristic

·Tank structure,strong,can bear the pressure test of an atmospheric pressure,there is no storage tank lid tank walls on both sides of the welding of high and low voltage cable junction box,for the use of cable wiring.High voltage coil with rated voltage and the voltage of plus or minus 5%points,using tap-changer transform voltage,voltage transformation must cut off power supply first,and then remove the box wall tap-changer change points after the storm of the hood.

·the low voltage side of transformer to allow "Y"shaped into 690 v power supply,also can convert into a delta form into 400 v power supply.the cable terminal box directly to the subprime end raises six porcelain jacket for modified by the user.

·The lift,the transformer is to use the box wall hanging welding by mixing,transformer with the car at the bottom of bracket,equipped with mounting holes on the bracket,for the mine will be required to have car wheel.

Technical Parameters

(kVA)RatedCapacity Voltage Marks (W)No-LoadLoss (W)On-LoadLoss (%)Shortcirait-z (W)No-LoadCur (kg)Weight (mm)Size (mm)Guage
(kV)H-V (%)Chng (kV)L-V Wain w.t Oil w.t Ttl w.t No Protective cover
50 106.36.0 ±5%or±2x2.5 0.4 Yy0(d11) 135 870 4 2.0 215 95 430 1150x730x980 400x200
100 230 1500 1.6 325 170 695 1220x940x1070 450x240
125 270 1800 1.5 365 185 790 1290x950x1080 450x240
160 320 2200 1.4 440 205 890 1220x950x1090 550x260
200 385 2600 1.3 515 225 1010 1340x970x1090 550x260
250 465 3050 1.2 600 255 1170 1430x1030x1100 550x280
315 535 3650 1.1 715 280 1325 1530x1110x1170 550x280
400 640 4300 1.0 850 325 1565 1590x1130x1300 550x300
500 770 5150 1.0 980 350 1745 1670x1140x1300 660x300
630 960 6200 4.5 0.9 1110 395 1990 1820x1320x1300 660x320
800 1120 7500 0.9 1160 485 2210 1870x1340x1450 660x320
1000 1360 10300 0.8 1315 600 2575 1910x1490x1500 660x320

inquiry